Modbus 4 opto-coupled, 9 relay outputs and 3 temperatures and humidity measurement unit

 

 

 

 Dimensions: 145mm x 90mm x 70mm

Clickable on a DIN rail

 

General description

The ACC4I9O3TRHMod allows you

bullet

to acquire up to 4 optocoupled inputs states (free of voltage contact)

bullet

to control up to 9 relays

bullet

to acquire up to 3 temperature (which measure and precision range are dependant of the choosen model) and / or 3 humidities ranging from 0 to 100% RH.

 

The ACC4I9O3TRHMod is Modbus compatible.

 

The inputs 

The inputs are optocoupled, giving the state of a voltage free contact.

 

The outputs 

The outputs are 230V/2A NO one contact relays.

 

Temperature and humidity measurement 

The measurement of temperature and humidity is done with digital sensors communicating with the ACC4I9O3TRHMod. Due to the digital nature of the dialog between the sensor and the ACC4I9O3TRH, the communication is very robust. The precision does not depent on the wires length neither on the connections.

 

Temperature only measurement

In using temperature sensors, only the temperature information will be available.

The measurement of temperature  is done with digital sensors communicating with the ACC4I9O3TRHMod. Due to the digital nature of the dialog between the sensor and the ACC4I9O3TRH, the communication is very robust. The precision does not depent on the wires length neither on the connections.

Compatible with all our program temperature sensors (based on DS18B20 or on Pt1000).

 

The sensors are connected to the ACC4I9O3TRHMod on a screw connector.

 

Modbus

Baud rate: 2400 bauds to 19200 bauds.

Address 1 to 255 (the adresse 0x3A or 58 is not available, it is the start of message in ascii mode).

2 or 4 wires with or without termination resistor.

RTU or ASCII dialog.

Recognized commands: command 03 (read register(s)), command 06 (write register), command 16 (write register(s))

Registres allocation for command 03:

Register Number (decimal)

Content

          0

Sensor 1 Temperature in tenth of Celcius degree

          1

Sensor 1 Humidity in %RH

          2

Sensor 1 status

     LSB : temperature part status:

          0: sensor OK

          1: sensor shorted

          2: no sensor

          3: temperature reading crc error

          4: reset condition

          5: sensor identification code reading crc error

     MSB : humidity part status:

          0: sensor OK

          1: sensor shorted

          2: no sensor

          3: humidity reading crc error

          5: sensor identification code reading crc error

          3

Sensor 2 Temperature in tenth of Celcius degree

          4

Sensor 2 Humidity in %RH

          5

Sensor 2 status

     LSB : temperature part status:

          0: sensor OK

          1: sensor shorted

          2: no sensor

          3: temperature reading crc error

          4: reset condition

          5: sensor identification code reading crc error

     MSB : humidity part status:

          0: sensor OK

          1: sensor shorted

          2: no sensor

          3: humidity reading crc error

          5: sensor identification code reading crc error

          6

Sensor 3 Temperature in tenth of Celcius degree

          7

Sensor 3 Humidity in %RH

          8

Sensor 3 status

     LSB : temperature part status:

          0: sensor OK

          1: sensor shorted

          2: no sensor

          3: temperature reading crc error

          4: reset condition

          5: sensor identification code reading crc error

     MSB : humidity part status:

          0: sensor OK

          1: sensor shorted

          2: no sensor

          3: humidity reading crc error

          5: sensor identification code reading crc error

          9

Inputs states:

          Bit0: state of input 1 (0 = input shorted)

          ........

          Bit3: state of input 4 (0 = input shorted)

 

Registers allocation for commands 06 and 16:

Register Number (decimal)

Content

          0

States to write on the outputs

          Bit0: state of output 1 (1 = relay activated)

          ........

          Bit8: state of output 9 (1 = relay activated)

 

Power supply:

The ACC4I9O3TRHMod is powered by a 8 to 35V DC voltage.

 

Avantages

bulletInnovative solution for inputs / outputs and temperature / humidity management.
bulletModbus interface.
bulletLow price

 

Downloads

File

Content

 

 

 

Price

Description Reference

Price

ACC4I9O3TRHMod Modbus 4 inputs 9 outputs 3 Temp And Humidity Sensors E07502 contact us
Regulated power supply 230VAC -> 24VDC/0.5A ESC-1.24.050S CHF 35.--
     