[Logo de l'entreprise] 

GSM Remote Ctrl Temp - Humidity Solar Sensors Leds lighting, Dmx Modbus DmxMidi General

SC2T1TRH
Remonter ACC8TMod ACC8T8RHMod SCTRH SC2T1TRH ACC4I6O6TRHMod ACC4I9O3TRHMod THS10 TS06-U

 

 

Remonter

 

Signal conditioner for 2 temperature and 1 temperature / humidity sensors

 

 

 Dimensions: 67mm x 77mm x 40mm

Clickable on a DIN rail

 

 

General description

The SC2T1TRH allows you to measure  up to 3 temperature (which measure and precision range are dependant of the choosen model) and / or 1 humidity ranging from 0 to 100% RH and to output the results in analog voltages.

Four outputs are provided:

- one T1 temperature sensor output,

- one T2 temperature sensor output,

- one TRH sensor temperature output,

- one TRH sensor humidity output

 

Temperature and humidity measurement 

The measurement of temperature and humidity is done with digital sensors communicating with the SC2T1TRH. Due to the digital nature of the dialog between the sensor and the SC2T1TRH, the communication is very robust. The precision does not depent on the wires length neither on the connections.

 

Temperature only measurement

In using temperature sensors, only the temperature information will be available.

The measurement of temperature  is done with digital sensors communicating with the SC2T1TRH. Due to the digital nature of the dialog between the sensor and the SC2T1TRH, the communication is very robust. The precision does not depent on the wires length neither on the connections.

Compatible with all our program temperature sensors (based on DS18B20 or on Pt1000).

 

Output ranges

The output ranges are configurable with 4 dil switchs as follows:

S1 S2 S3 S4 Range
OFF OFF OFF OFF 10mV/°C (0°C=0V) & 10mV/%RH (0%RH=0V)
OFF OFF OFF ON 20mV/°C (0°C=0V) & 20mV/%RH (0%RH=0V)
OFF OFF ON OFF 40mV/°C (0°C=0V) & 40mV/%RH (0%RH=0V)
OFF OFF ON ON 80mV/°C (0°C=0V) & 80mV/%RH (0%RH=0V)
OFF ON OFF OFF 0 to 5V 25mV/°C (0°C=1V5) & 50mV/%RH (0%RH=0V)
OFF ON OFF ON

Special: temperature restriction 0 to 100°C

 (below 0°C output is 0V,

  above 100°C, output is 5V)

0 to 5V 50mV/°C (0°C=0V) & 50mV/%RH (0%RH=0V)

         
ON OFF OFF OFF 0 to 10V 50mV/°C (0°C=3V) & 100mV/%RH (0%RH=0V)
ON OFF OFF ON

Special: temperature restriction 0 to 100°C

 (below 0°C output is 0V,

  above 100°C, output is 10V)

0 à 10V 100mV/°C (0°C=0V) & 100mV/%RH (0%RH=0V)

         
         

All the not listed possibilities give OFF/OFF/OFF/OFF values.

 

Others possibilities are still available for special needs.

 

Output voltages précision

The used D/A converters having more bits than the sensors, the sensor's precision is kept.

 

Power supply

The SC2T1TRH is powered with a DC voltage between 8 and 35V.

 

Case

Le SC2T1TRH is mountable on a DIN rail

 

Advantages

bulletInnovative solution for temperature and/or humidity measurement.
bulletNo configuration needed (except the output range)
bulletLow price

 

Downloads

File

Content

 

 

 

Price

Description Reference

Price

SC2T1TRH Signal conditioner for 2 temperature and 1 temperature / humidity sensor E07511 contact us
Regulated power supply 230VAC -> 24VDC/0.5A ESC-1.24.050S CHF 35.--
     

For more information: info@pongo.info

 

Please send an email to  webmaster@pongo.info for any questions or suggestions regarding this Web Site.

Envoyez un courrier électronique à webmaster@pongo.info pour toute question ou remarque concernant ce site Web.

Last modification / dernière modification : 29 mai 2024